FAQs

Hoods

  • Only use mild detergents to clean stainless. DO NOT use any cleaner with chlorine. Use a soft rag. DO NOT use any abrasive pads or steel wool.

  • Filters should be cleaned as often as necessary. Clogged filters don't work efficiently and aremore difficult to clean. Where heavy charbroiling is done you should clean every day. If you are only baking you may only need to clean weekly. What's important is to set up a schedule and clean accordingly.

  • The hood lights burn out often.

Excessive vibration will cause standard incandescent bulbs to fail early. Replace with rough service bulbs. Another cause is poor contact with the brass tab in the bottom of the light socket. This will cause the bulb to overheat at the point of contact. This is usually a small amount of solder at the base of the bulb. This solder may melt allowing air to enter the bulb. Once air replaces the inert gas in the bulb the tungsten element oxidizes and the bulb fails. You can tell this has happened by the smoky grey deposits inside the bulb Adjust the tab in the light socket so that it is about 1/4" above the bottom of the socket. Loose wires in the light socket may also result in bulb failure.

  • Stainless steel doesn't rust under normal conditions. Stainless gets its non corrosive properties from the chromium in the alloy. The chromium atoms form a passive surface film over the base steel very much like the paint protects your car. Once this layer is removed the base metal is exposed to the moisture in the atmosphere and rust forms. Chlorine in any form combines with the chromium and removes this protective layer and exposes the base metal and rust will occur. NEVER use any chemicals that contain chlorine near any stainless. This includes any cleaners, acids to clean quarry tile or brick, and some detergents. Even the vapors can attack stainless steel. Never use steel wool to clean stainless. Particles of the steel wool will get trapped in the grain of the stainless and these steel particles will rust.

  • There could be something in the grease trough that is preventing the grease from draining. Remove filters and check the trough. Grease troughs should be cleaned frequently to remove any solid sediment that accumulates restricting the flow of grease.

  • This water is entering the fixture from above. The glass globe is gasketed and if it is on tight water cannot enter form below. The probable cause of this is the duct is leaking. Look at the top of the hood above the ceiling and if you see puddles of water and grease on top of the hood, the duct has a leak. If the duct in not insulated you will probably see some areas, especially in the corners, that look wet.

  • There is probably a leak in the duct allowing grease to collect on top of the hood and it is draining into the fixtures. Check the top of the hood above the ceiling. Any puddles of grease or water indicate there is a leak in the duct.

  • Yes, both are Nationally Recognized Testing Laboratories that test, certify and inspect products for safety and performance for manufacturers. The standard to which our hoods are tested is UL 710, Exhaust fans are tested to UL Standards UL 762 & UL 705 . You can visit this link for a comparison.

  • Incandescent light bulbs: 100 Watts max, clear bulb (not frosted)

    3' Fluorescent: F25T8, 25 Watts, T-8 Ballast

    4' Fluorescent: F32T8, 32 Watts, T-8 Ballast

    Compact Fluorescent:

    Lamp type: Compact Fluorescent - Self-Ballasted

    Bulb: T3

    Base: Medium Screw (E26)

    ENERGY STAR® Qualified: Yes

    Wattage: 26

  • First lift one filter in the track and moving it toward the back of the grease plenum rest it in the trough with the top leaning o the back of the grease plenum, filter should be standing near vertical and away from filter track. Next side remaining filter over and remove this filter as normal, then reach into plenum and remove the first filter.

Fans

  • There is an adjustable sheave on the motor. There are two hex set screws on the pulley. One secures the pulley to the shaft. The other allows the two halves of the pulley to be adjusted closer together or further apart. Be sure when adjusting retighten the set screws on a flat side of the pulley base. Adjusting the halves closer together increases the fan speed, further apart slows it down. Double grove pulleys must be turned the same number of turns or the belts will not seat properly in the groves. Always check motor amperage after adjusting pulleys.

  • Yes, most fan models can be ordered this way. This is called a fan shell. It is a complete fan less the drive package. The drive package is the motor, pulley, and belts.

  • Single groove pulleys are usually easy to remove after loosening the set screw. Larger pulleys that have a tapered compression bushing are removed by taking out the two hex bolts and placing them in the other two holes. When tightened the bushing will pop out and the pulley can be removed. When replacing make sure the taper of the pulley and bushing match.

  • Several things can cause vibration. Before assuming the wheel is unbalanced, check other possible causes first. Look for any obvious signs of a rag or foreign object stuck in the wheel. Another common problem is the fan was recently cleaned and not all the grease was removed from the wheel causing it to be out of balance. Mechanical problems can be the motor, belt, bearings, or wheel. Remove the belt and run only the motor if it vibrates replace motor. Check the belt. If it is in poor condition replace. Make sure the blower pulley and the motor pulley are in alignment. Check bearings for wear or damage. They may also need lubrication. Finally make sure that the fan is secured to the curb. Just adding an extra screw can sometimes quite a noisy fan. If a fan is operating outside its performance range it will also vibrate.

  • First you need to verify if the water is leaking inside or outside the duct. If the water is inside the exhaust plenum, the area behind the filters, the grease drain on the fan may be clogged and the water is overflowing the venturi on the lower baffle assembly. For a parts breakdown, see the Exploded Parts Detail. The silicon seal between the baffle assembly and the fan base could also be the cause of the leak. If the water is leaking outside the duct and is dripping on the outside of the plenum or collecting in the light fixtures the problem is probably the curb was not flashed to the roof properly.

  • The motor is probably shutting off on thermal overload. The motor is overheating and restarts after it cools down and the thermal overload resets. This only happens with single phase motors that are thermally protected. The name plate will tell you if it has internal protection. First measure the amp draw while the motor is running and compare it with the nameplate. If it is not much higher you may only need to slow the fan down until it is at or below the running amps indicated on the name plate. If slowing the fan down is not an option you need to replace the motor with a larger HP motor. Lastly it could be a defective motor.

  • The overload provides protection for motors without internal thermal protection. This is on all three phase and large single phase motors. If a motor over amps or the current draw on the incoming power leads is unbalanced the overload will trip. Overamping can be the result of using a motor not large enough or running the fan at higher RPM's than needed. If you can slow the fan down this should be your first choice. If this is not an option replace the motor with a larger HP one. Unbalanced loads can be the result of a defective motor or unbalanced power supply. If one of the lines of a 3-phase power supply has lost it's voltage the motor will run on only two lines and overamp. Another common cause of overload tripping is a lightening storm or power outage. When the power comes on again voltage is usually low because of the great demand on the power grid. As voltage goes down the amperage goes up and the overload trips.

  • This could be the result of a loose or worn belt. Other possible causes are dirty or clogged filters or the fan wheel is loaded with grease.

  • This could be the result of a loose or worn belt. Other possible causes are dirty or clogged filters located in the unit on the roof.

  • If the hood system was provided with our control panel the system is probably in fire condition. In this mode the exhaust fan will not shut off and the supply fan will not come on. Other possible causes are the R1 relay is bad in the control panel, the fan switch is defective, or the contactor is stuck in the closed position.

  • If the hood system was provided with our control panel the system is probably in fire condition. In this mode the exhaust fan will not shut off and the supply fan will not come on. Other possible causes are the R1 relay is bad in the control panel, or the contactor coil is open.

  • Super Filter Coat is a water soluble adhesive applied to the mesh filter after each washing. The adhesive is characteristic of fly paper as it will trap the dust and dirt particles from the airstream. This is available from our website. It is part number 412.

  • Yes, both are Nationally Recognized Testing Laboratories that test, certify and inspect products for safety and performance for manufacturers. The standard to which CAS hoods are tested is UL 710, Exhaust fans are tested to UL Standards UL 762 & UL 705. You can visit this link for a comparison.

  • On direct drive motors the FLA listed on the nameplate is the amperage at its highest speed. The speed control reduces the speed of the motor by lowering the voltage supplied. Basic electric laws dictate that when you decrease the voltage the amperage increases. This is normal for these types of motors. Speed controls used on direct drive fans are rated higher than the motor to accommodate this increase.

  • All motors are suitable for high and low voltage applications. Single phase motors are rated 115/208-230. This means the low voltage is 115 volts and the high is 208-230. Similarly three phase motors are rated 208-230/460. This means that the low voltage is 208-230 and the high voltage is 460. To change the supply voltage, refer to the diagram on the motor label for wiring instructions. If a prewire is included on the job you will need to replace the contactors and/or overloads because of the change in FLA (refer to the motor label). If the supply fan is a heater, one will need to rewire the KVA transformer for the new voltage. NOTE: A single phase motor cannot be converted to three phase and a three phase cannot be converted to single phase. The motor must be replaced.